Service and Meter Installation Requirements Guide

08.05   UNDERGROUND NETWORK SYSTEM AREAS

SERVICE VOLTAGE

 

The standard service supplied by the Company is alternating current with a nominal frequency of 60 hertz. Not all types of service listed below are available at all locations, and service voltages other than secondary may be specified by the Company under special conditions such as may relate to the location, size, or type of load.

SECONDARY DISTRIBUTION VOLTAGE IN THE ESTABLISHED UNDERGROUND NETWORK SYSTEMS AREAS IN THE CITIES OF ALTOONA, ASBURY PARK, EASTON, ERIE, JOHNSTOWN, LEBANON, MORRISTOWN, READING AND YORK

Wiring type and location

Voltage

Single-Phase, 3-wire, wye
(from network system)

120/208

Three-Phase, 4-wire, wye for loads of 300 KVA or less
(from network system)

120/208

Three Phase, 4-wire, wye for loads from 300 KVA to 750 KVA
(at the Company's determination from the network or separate transformer)

120/208

Three Phase, 4 wire, wye for loads from 750 KVA to 1500 KVA from separate transformer. (750 KVA to 1000 KVA for Asbury Park, Altoona 2400/4160, Easton network area).

277/480

PRIMARY DISTRIBUTION VOLTAGES IN THE ESTABLISHED UNDERGROUND NETWORK SYSTEM AREAS IN THE CITIES OF: ALTOONA, ASBURY PARK, EASTON, ERIE, JOHNSTOWN, LEBANON, MORRISTOWN, READING AND YORK

Wiring type and location

Voltage

Three Phase, 4 wire, wye(Altoona, Asbury Park)

2400/4160

Three Phase, 3 wire, delta ( Easton)

4,800

Three Phase, 3 wire, delta (Erie)

12100

Three Phase, 4 wire, wye (Altoona, Morristown)

7200/12,470

Three Phase, 4 wire, wye ( Lebanon, Reading and York)

7,620/13,200

Three Phase, 4 wire, wye (Johnstown)

13200/22,860

There are other underground areas in the Company such as Summit, Pompton, Allenhurst, Redbank, etc. that shall have services installed in the same manner as network systems areas.

End of Specification: