08.10   NETWORK SINGLE-PHASE AND THREE-PHASE SERVICE

SINGLE-PHASE SERVICE

All single-phase underground single and multiple meter installations shall have 100 ampere, 3-wire service entrance equipment as a minimum for each meter location. Service size in excess of 400 amperes shall have transformer rated services.

THREE-PHASE SERVICE

All overhead polyphase single and multiple meter installations shall have 100 ampere, 4-wire, wye service entrance equipment as a minimum for each meter location.

All polyphase underground single and multiple meter installations shall have 100 ampere, 4-wire, wye service entrance equipment as a minimum for each meter location. Services sizes in excess of 400 amperes shall have transformer rated services.

End of Specification: